Dimmer Load Calculator for Stage Lighting

Dimmer Load Calculator

Estimate fixture wattage, channels, voltage, dimmer pack rating, channel rating, diversity, load percentage, and stage circuit current before patching a lighting rig.

🎭 Lighting Presets

Pick a realistic starting look, then edit the wattage, channel count, dimmer rating, diversity, and circuit limits to match the actual venue, rack, or touring dimmer pack.

Dimmer And Load Inputs
Applies a typical power factor and load warning.
Nameplate lamp or fixture input wattage.
Number of identical fixtures patched to each dimmer channel.
Channels carrying this load group.
Use the actual branch voltage at the dimmer input.
Common stage channels are 1.2 kW, 2.4 kW, or 6 kW.
Main feed, camlock leg, or dimmer pack input rating.
Usable branch circuits feeding this dimmer load.
Use breaker or overcurrent protection rating.
Continuous lighting loads are often planned at 80 percent.
How much of the plot is expected to be on at once.
Full-intensity check is 100 percent.
Tungsten is near 1.00; LED or transformer loads may be lower.
Reports total current and an estimated leg current.
Fan trays, dimmer electronics, work lights, or small practicals.
Connected Load
0 W
fixture wattage before diversity
Active Show Load
0 W
after dimmer level and diversity
Circuit Current
0 A
estimated current per branch circuit
Highest Utilization
0%
channel, pack, or circuit limit
📊 Dimmer Spec Grid
1.2 kW

10 A channel at 120 V

2.4 kW

20 A channel at 120 V

3.68 kW

16 A channel at 230 V

6.0 kW

50 A channel at 120 V

🔌 Channel Rating Table
Channel rating120 V watts230 V watts80 percent planning loadTypical use
10 A1,200 W2,300 W960 W at 120 VSmall packs, practicals, single fixtures
15 A1,800 W3,450 W1,440 W at 120 VLight-duty architectural dimming
16 A1,920 W3,680 W2,944 W at 230 VCommon EU stage dimmer channel
20 A2,400 W4,600 W1,920 W at 120 VStandard 2.4 kW theatre channel
50 A6,000 W11,500 W4,800 W at 120 VHigh-capacity rack channel or relay feed
💡 Fixture Load Reference
Fixture or lampCommon wattage120 V current230 V currentDimmer note
MR16 practical cluster150 W to 300 W1.3 A to 2.5 A0.7 A to 1.3 AWatch transformer compatibility
PAR 56 or small fresnel300 W to 500 W2.5 A to 4.2 A1.3 A to 2.2 AOften safe as singles or pairs
575 W ellipsoidal575 W4.8 A2.5 AThree units can exceed 80 percent on 20 A at 120 V
750 W ellipsoidal750 W6.3 A3.3 ATwo per 20 A channel is a common planning limit
1 kW fresnel or PAR1,000 W8.3 A4.3 ATwo per 20 A channel is above 80 percent at 120 V
2 kW studio fixture2,000 W16.7 A8.7 AUsually needs a full 20 A channel at 120 V
🎧 Preset Load Comparison
PresetFixture wattsChannelsVoltagePlanning concern
Coffeehouse Fresnels300 W4120 VSmall load, but shared circuits still matter
Black Box Rep Plot575 W12120 VChannel loading is usually the first check
Church Warm Wash750 W8120 VBranch circuits can fill quickly during full looks
School Stage Pack500 W12120 VPortable packs need feed and neutral verification
Opera House Tungsten1,000 W60120 VRack input and phase balance dominate
Diversity And Circuit Guide
Use caseDiversityAverage levelCircuit limitWhat to verify
Full work light or focus mode100 percent100 percent80 to 100 percentWorst-case channel and branch current
Typical theatre cueing60 to 80 percent65 to 90 percent80 percentBrightest cue, not just average scene
Club chase looks45 to 70 percent45 to 80 percent80 percentStrobe, chase, and blackout recovery loads
Architectural practicals70 to 95 percent40 to 75 percent80 percentLamp type and dimmer minimum load
Mixed LED retrofit dimming50 to 90 percent30 to 75 percent70 to 80 percentPower factor, leakage, and relay bypass needs
Channel tip: Check the per-channel connected wattage at full intensity before applying diversity. Diversity helps service planning, but it does not make an overloaded channel safe.
Circuit tip: Compare the calculated current with real clamp-meter readings during the brightest cue. Dimmers, neutral loading, and shared venue circuits can change the field result.

Lighting crew must understand how to calculate electrical loads to ensure that there dimmer pack dont fail. A dimmer pack will fail if there is an electrical overload within the dimmer packs, which usually happen during a lighting cue that requires the lights to be at their maximumly brightness. Two ways to prevent a dimmer pack failure is to understand the load on each lighting channels and to understand how diversity, dimmer level, and power factor affect the load on those channels.

Fixture wattage are the first calculation to perform to determine the load on each channel. However, fixture wattage is not the only calculation that must be performed. The number of light on each channel and the voltage of the lighting installation also must be considered.

How to Calculate Lighting Loads to Avoid Dimmer Pack Failure

Using a lighting load calculator will make it easier to determine the load on each channel without guessing if the wattage of the lamps will remain within an 80 percent planning limit for the dimmer packs. The channel rating will also provide information that will help lighting designer determine the load on each channel. For example, lighting designers can plan for a 20 amp channel to carry 2400 watts at 120 volts, but they may plan for 1920 watts so that the dimmer rack will not overheat while the technical rehearsal run for the show.

The same is true for the pack input, where lighting technician must account for any spare cable and work lights that may be connected to the lighting installation. Another factor that can be used to calculate the load on the lighting installation is diversity. Diversity is the percentage of the installation that is on at one time.

Many lighting plots will use 75 percent diversity for most of the show, but 90 percent diversity for the finale of the show. Tester will use a lighting load calculator to plan for diversity so that the lighting installation wont fail under the planned show. Power factor is another calculation that lighting crews must consider, especially with the increasing use of LED fixtures and low voltage transformer.

Tungsten light will have a power factor that remains close to unity. LED lights will have a power factor of 0.9 or lower. The power factor will help lighting crews determine how much current is in the dimmer rack and the neutral wire, which can be read with a clamp meter.

By calculating the power factor, the current that is measured will equal the current that is calculate. Circuit planning for lighting installation uses the same logic as dimmer packs. Most venue will provide 20 amp circuits.

However, the load must remain within 80 percent of the calculated load because the circuits will be on for many hours during the show. If the current that is calculated for each circuit is more than 80 percent of the current limit, the lighting technician will have to use another circuit or the lighting patching plan will have to be change. A lighting load calculator will provide a recommendation for a new circuit or a patching plan before the lighting installation begins.

Unfortunately, not all factor can be accounted for in the lighting load calculator. Some factor that can change the load on the lighting installation include shared neutral, voltage drop in the cables, and the age of the dimmer racks. To determine if the electrical calculations were accurate, lighting technician will use a clamp meter to measure the current in the brightest lighting cue of the show.

The current that is measured will be compared to the calculated current to determine if the calculations were accurate. Another instance during which a clamp meter should of been used is to switch from tungsten lights to LED lights. LED lights will have a lower wattage reading, but they may create an inrush current that will trip an older dimmer pack.

The clamp meter will help to detect this problem. The lighting load calculator will provide the lighting designer with a baseline for the calculations, but the clamp meter will provide measurement to determine if there are any issue with the lighting installation. It is a habit for lighting installer to perform the electrical calculations for the lighting installation twice.

The calculations can be performed once at 100 percent diversity and the second time with the calculated diversity and dimmer levels for the show. The calculations at 100 percent diversity will allow the lighting designer to determine if the load on the dimmer packs can survive an error in the lighting plot. The calculation at the diversity and dimmer levels will allow the lighting designer to determine if the lighting plot will be compatible with the power provided by the dimmer packs.

By calculating the load on the lighting installation twice, the lighting designer will be certain that they will finish the lighting installation in the time allotted for the show.

Dimmer Load Calculator for Stage Lighting

Leave a Comment