NTC Curve Calculator for Transmission Loss

NTC Curve Calculator

Fit a Noise Transmission Class contour from one-third octave transmission loss data, then inspect the summed and single-band deficiencies that control the rating.

🎧Curve Presets
📏Measurement Setup
For NR input, corrected transmission loss is TL = L1 - L2 + 10 log10(S/A), where S is test specimen area and A is receiving room absorption. The NTC fit then shifts the reference contour to the highest rating where total deficiency is no more than 32 dB and no single band is more than 8 dB.
🎛One-Third Octave Band Values
Noise Transmission Class
NTC 50
500 Hz contour rating
Total Deficiency
0 dB
limit 32 dB
Weakest Band
125 Hz
largest deficiency
Average Corrected TL
49 dB
125 Hz to 4 kHz
📊Spec Grid
16
Bands Scored
32 dB
Sum Deficiency
8 dB
Single Band Limit
500 Hz
Rating Anchor
📋Current Deficiency Breakdown
BandCorrected TLContour TLDeficiency
125 Hz31 dB34 dB3 dB
250 Hz41 dB43 dB2 dB
500 Hz50 dB50 dB0 dB
1000 Hz53 dB53 dB0 dB
📐Reference NTC Contour
Frequency BandContour OffsetNTC 50 ContourScoring Use
125 Hz-16 dB34 dBLow-frequency wall mass check
250 Hz-7 dB43 dBLow-mid coincidence and cavity check
500 Hz0 dB50 dBRating anchor band
1000 Hz+3 dB53 dBSpeech isolation control band
2000 Hz+4 dB54 dBUpper-band leakage check
4000 Hz+4 dB54 dBSeal and flanking sensitivity check
🧱Assembly Comparison Table
Assembly TypeTypical NTC RangeCommon Weak BandBest Use
Single stud drywall wallNTC 32 to 42125 to 250 HzLight isolation between practice spaces
Resilient channel wallNTC 42 to 52160 to 315 HzImproved speech and instrument separation
Double stud isolated wallNTC 55 to 68125 to 200 HzRecording rooms and loud rehearsal rooms
Solid masonry partitionNTC 45 to 60Coincidence dip variesHigh mass isolation with controlled flanking
Acoustic door setNTC 35 to 55500 to 2000 HzMaintaining wall rating at openings
Laminated acoustic glassNTC 38 to 521000 to 3150 HzStudio sightlines and control room windows
🎵Common Audio Isolation Scenarios
ScenarioSuggested TargetPrimary ConcernCurve Check
Home studio vocal boothNTC 45 to 55Speech and headphone bleedWatch 500 Hz to 2 kHz deficiency
Drum practice roomNTC 60 to 70Kick and tom energyWatch 125 Hz and 160 Hz deficiency
Control room windowNTC 40 to 50Glass coincidence regionCheck 1 kHz to 3.15 kHz dip
Stage-to-lobby partitionNTC 50 to 60Amplified music leakageCheck total deficiency after correction
Podcast suite demising wallNTC 48 to 58Voice privacyCheck 250 Hz to 1 kHz smoothness
📘Formula Reference
FormulaExpressionInputsMeaning
Transmission loss from NRTL = NR + 10 log10(S/A)S area, A absorptionCorrects level difference to a test-style TL curve
Noise reductionNR = L1 - L2Source and receive levelsMeasured room-to-room level difference
Band deficiencyDef = max(0, contour - TL)Contour and corrected TLOnly unfavorable gaps count against rating
NTC acceptanceSum def <= 32 and max def <= 8All 16 bandsHighest passing contour becomes the NTC rating
💡Calculation Tips
Curve fit tip: A higher average TL does not guarantee a higher NTC rating. One deep dip can stop the contour shift even when the rest of the bands look strong.
Field correction tip: When entering NR instead of TL, keep specimen area and receiving absorption in the same test condition. A wrong S/A correction can move every band up or down together.

An NTC rating is a single number that represent the sound insulation performance of an assembly, such as a wall, a door, or an window. The NTC rating is useful in that it can convert all of the different measurement of the transmission loss of a construction element to a single number that can be used to make a decision about that construction element. The NTC rating isnt the average of all of the measurements of the sound insulation properties of that element.

Instead, the NTC rating uses two rules to arrives at the number for that element. The first rule is that the total shortfall of all band must be no more than 32 dB. The second rule is that no band can exhibit a shortfall of more than 8 dB.

What the NTC rating is and how it works

These two rules are important in that they ensures that no construction element has a high NTC rating due to having a major leak of sound at a single frequency. The NTC rating is determined by plotting the performance of an element as a contour with an anchor at 500 Hz. All other frequency bands is plotted at a fixed offset either above or below the 500 Hz anchor.

The low frequency bands are plotted below the 500 Hz anchor due to the mass and stiffness of the materials at those frequencies. The higher frequency bands are plotted above the 500 Hz anchor because materials naturaly exhibit higher sound insulation at higher frequencies. Each measurement of the sound insulation performance of an element is entered into a calculator that shifts the entire contour up or down until it passes both rule for the NTC rating.

The highest NTC rating that meet both rules is the NTC rating that can be assigned to the construction element. The various inputs into the calculator will determine whether the values entered are laboratory measurements of sound transmission loss or field measurements of noise reduction. Sound transmission loss accounts for both the area of the test specimen and the absorption of sound in the receiving room.

Noise reduction does not account for either the area of the test specimen or the absorption of sound in the receiving room. Thus, you must correct noise reduction values for area and receiving room absorption before they are entered into the calculator. Without making this correction, the values that are entered into the calculator will exhibit incorrect values for the NTC rating.

Many people make the mistake of not making this correction, leading to incorrect NTC ratings that dont match the laboratory measurements of sound transmission loss. The various construction assemblies that are evaluated with the NTC rating will rarely have smooth sound transmission loss curves. Most building assemblies will have weak points at specific frequency.

For instance, a single stud wall with two layers of drywall will exhibit weak sound isolation between 125 Hz and 250 Hz. This weak point result from the mass air mass resonance of the drywall on each side of the stud. This weak point will prevent the sound isolation performance of that wall construction from receiving an NTC rating that is high relative to other construction elements in a building.

If the studs are isolated from the drywall, or if resilient channels are installed between the drywall and studs, the sound isolation between those two bands will improve, potentially increasing the NTC rating of that wall by eight to fifteen points. These comparison can be made with the calculator. Doors and glazing will exhibit the same type of weakness in their sound isolation performance.

For instance, an acoustic door may exhibit high ratings for sound isolation above 500 Hz, but the NTC rating of that door may be low due to the seals around the perimeter of the door. Likewise, laminated glazing may have high sound isolation values for most frequencies, but at 2000 Hz the sound insulation will be less due to the coincidence between the wavelength of sound at 2000 Hz and the thickness of the glass. The narrow bandwidth of these weak areas is why the limit is placed on the single band shortfall to 8 dB.

Without that limit, a manufacturer may produce a product with high sound isolation performance except at certain frequency where sound can escape the door or glazing. Field measurements of sound isolation may be different than measurements taken in the laboratory. For instance, the absorption in a receiving room may be different from the absorption in a sound transmission loss test room.

The absorption in the field may be affected by the presence of furniture, carpeting, or people in the space. The sound levels of the sound source may also be different from those in a test room. For instance, a drum kit will contain high levels of sound in the 125 Hz band while a podcast microphone will exhibit low sound levels at that frequency.

The ability to enter optional sound source and receiving room levels is important to convert sound reduction to transmission loss. This ability to enter these levels is important because it will prevent the comparison of two different types of measurements from being made. The target NTC rating for a construction element should be based off the use case of the rooms that utilize that construction element, not upon the material of that construction element.

For instance, a vocal booth in a home may require an NTC rating of around 45 to 50 to prevent the sound of headphones from entering a microphone. In contrast, a room that is to be used for practicing playing drums may require an NTC rating of around 60 because sound at low frequencies is to be controlled in that room. Thus, if the calculated NTC rating is three points above the target, the construction element has breathing room.

If, however, the calculated NTC rating is three points below the target, the construction element can be evaluated to determine at which frequencies the sound isolation is failing. While the NTC rating is a helpful measurement for construction elements, the NTC rating should not be considered to be a guarantee of the performance of that construction element. The performance of a construction element in the real world can be affected by flanking paths for sound, the installation of the construction element, and the structure of the building in which that construction element is installed.

Furthermore, the NTC rating is based upon sixteen one-third octave bands between 125 Hz and 4000 Hz. Any deviation from this banding will invalidate the comparison of NTC ratings between construction elements. Thus, the banding used in measuring sound isolation should be kept the same between all tests to ensure that the measurement of sound isolation is accurate and reliable.

Reference tables exist that display the NTC ratings that is achieved by various construction elements. For instance, single stud walls tend to have NTC ratings of around the low forties. Double stud systems that are isolated from the drywall have NTC ratings that can reach the low sixties.

Masonry walls are somewhere in between these two construction elements. Furthermore, the coincidence dips in masonry walls tend to exhibit at different frequencies from those of lightweight construction elements. These reference tables may help to set expectations for a construction element, but they are not a replacement for measuring the sound isolation of the individual construction elements.

Overall, the NTC rating will help to indicate whether or not the construction of a wall or a door will meet the goal that is set up for its sound isolation performance. If the NTC rating for the construction element is high enough, the construction element can be built with confidence. If the NTC rating for the construction element is too low, the deficiency within that construction element can be evaluated to determine in which frequency bands the construction element will fail to provide the sound isolation performance that is required.

Thus, the NTC rating is a helpful tool for making decisions about construction elements and the sound isolation performance that they will achieve. The NTC rating for a construction element is useful in that it provides a single number to the building and sound isolation engineer and it also provides a look at the deficiency in that construction element.

NTC Curve Calculator for Transmission Loss

Leave a Comment